Forced ventilation fans maintain the correct temperature inside the cabinet by exchanging heated inside air for cooloutside air.

Advanteges:

  • Mount without screws into square openings using elastic clips
  • Replace the filter membrane from the outside without tools
  • Reversible airflow direction
  • Airflow up to 800 m³/h
  • Installation for plate thickness between 1,5 mm and 2,5
  • IP 54 standard rating
  • Wall and top mounting options
  • Operational temperature range from -10 °C to +70 °C
  • Permanent sealing gasket in polyurethane foam
  • UV protection
Where to buy
Print Favorities E-mail Twitter RSS
  • Air_flow_Filter fan_unitFilter fan unitFilter fan unitFilter fan unitFilter fan unitFilter fan unitFilter fan unit
  • Filter fan unit

Sizing:

When we use fan filters, we must have a target temperature inside the cabinet that is greater than the ambient temperature outside the cabinet (Te), which makes the difference (ΔT) between the inside and outside temperatures always positive. We can calculate the fan filtered airflow by taking the ratio between the thermal power (Q ) and the temperature difference (ΔT) and multiply that by the heat transfer coefficient (f ), which considers the physical properties of air, including heat and density which can change with altitude (m).

Recommendations for installation:

The filter fan unit should be placed in the lower part of the enclosure to allow the cool air to enter into the enclosure and form a slight overpressure. This means that air flows into the enclosure through the filter fan unit without any dirt/dust and removes warm air from the enclosure through the outlet filter grid. If the filter fan unit is installed in the opposite direction, dust and dirt can enter into the enclosure along with cool air. The filter fan unit should be placed in the bottom third of the cabinet and the outlet filter grid should be placed as high as possible. This will prevent the accumulation of warm air in the upper part of the enclosure.

Specifications:

  • Material: PC/ABS Alloy, PA 66 GH13 HSL for elastic clips
  • Color: RAL 7035
  • Protection degree: IP54 (IP55 using special filter mats, IP56 using hose-proof cover)
  • Fixing system: by elastic clips, otherwise by four self-thre adingscrews
  • Type of filter media: thermo-linked progressive structure with synthetic fiber
  • Filtering class: G3, according to EN 779
  • Dust retention capacity: 600 g/m2
  • Airflow direction: reversible
  • Filter media can be washed up to about 10 timest

Supply includes:

Unit with filter mat ready for connection.

Filter fans, air flow 12 - 100 m³/h       
Order code   ID-EF-01-4 ID-EF-01-1 ID-EF-04-4 ID-EF-04-1 ID-EF-10-4 ID-EF-10-1
Dimenssions in mm   H 106,5 106,5 150 150 203,9 203,9
L 106,5 106,5 150 150 203,9 203,9
D1 6,7 6,7 7,7 7,7 8 8
Max. installation depth i mm D2 59,9 46,9 65,5 65,3 87,5 87,3
Voltage/Frequency   230 V, 50/60 Hz 24 V DC 230 V, 50/60 Hz 24 V DC 230 V, 50/60 Hz 24 V DC
Rated current   62/50 mA 85 mA 110/100 mA 310 mA 106/100 mA 342 mA
Rated power   10/8,0 W 2,0 W 18/17 W 7,4 W 18/18 W 8,2 W
Max. air flow   12/15 m3/h 15 m3/h 45/50 m3/h 47 m3/h 100/110 m3/h 100 m3/h
Static pressuare   23/33 Pa 25 Pa 55/62 Pa 56 Pa 55/60 Pa 60 Pa
Fan noise   31/33 dB(A) 30 dB(A) 48/51 dB(A) 42,5 dB(A) 48/54 dB(A) 42 dB(A)
Weight   0,39 kg 0,39 kg 0,76 kg 0,45 kg 0,96 kg 0,64 kg
Lifetime   50 000 h 100 000 h 57 000 h 50 000 h 57 000 h 50 000 h
Rated temperature range   -10 to +55 °C -10 to +55 °C -10 to +55 °C -10 to +55 °C -10 to +55 °C -10 to +55 °C
Outlet filter grid Package ID-EF-01 ID-EF-01 ID-EF-03 ID-EF-03 ID-EF-05 ID-EF-05
Cut-out   91,5x91,5 mm 91,5x91,5 mm 125x125 mm 125x125 mm 177x177 mm 177x177 mm
Accessories Package            
Spare filter mats IP54 5 pcs ID-EF-F01 ID-EF-F01 ID-EF-F03 ID-EF-F03 ID-EF-F05 ID-EF-F05
Spare filter mats IP55 5 pcs ID-EF-F5505 ID-EF-F5505
Hose-proof cover 1 pc ID-EF-C01 ID-EF-C01 ID-EF-C03 ID-EF-C03 ID-EF-C05 ID-EF-C05
Plastic adaptors 1 pc ­ ­ ID-EF-A03 ID-EF-A03 ­ ­
EMC version and other input voltage options available upon request.  

 

Filter fans, air flow  230 - 710 m³/h    
Order code   ID-EF-23-4 ID-EF-22-1 ID-EF-52-4 ID-EF-71-4
Dimenssions in mm H 250 250 325 325
L 250 250 325 325
D1 8,9 8,9 9,5 9,5
Max. installation depth i mm D2 115,3 116,5 150,7 149
Voltage/Frequency   230 V, 50/60 Hz 24 V DC 230 V, 50/60 Hz 230 V, 50/60 Hz
Rated current   134/160 mA 710 mA 318/381 mA 650/820 mA
Rated power   32/36 W 17 W 73/87 W 150/190 W
Max. air flow   230/270 m3/h 225 m3/h 520/580 m3/h 710/800 m3/h
Static pressuare   115/155 Pa 99 Pa 160/185 Pa 195/205 Pa
Fan noise   50/55 dB(A) 58 dB(A) 65,3/68,1 dB(A) 72,8/75,8 dB(A)
Weight   1,5 kg 1,4 kg 3,1 kg 4,25 kg
Lifetime   80 000 h 100 000 h 65 000 h 70 000 h
Rated temperature range   -10 to +55 °C -10 to +55 °C -10 to +70 °C -10 to +60 °C
Outlet filter grid Order code ID-EF-07 ID-EF-07 ID-EF-09 ID-EF-09
Cut-out   224x224 mm 224x224 mm 292x292 mm 292x292 mm
Accessories Package        
Spare filter mats IP54 5 pcs ID-EF-F07 ID-EF-F07 ID-EF-F09 ID-EF-F09
Spare filter mats IP55 5 pcs ID-EF-F5507 ID-EF-F5507 ID-EF-F5509 ID-EF-F5509
Hose-proof cover 1 pc ID-EF-C07 ID-EF-C07 ID-EF-C09 ID-EF-C09
Plastic adaptors 1 pc ID-EF-A07 ID-EF-A07 ID-EF-A09 ID-EF-A09
EMC version and other input voltage options available upon request.